Costruire fiducia, garantire il successo Area clienti dang.victor@worldsteelgroup.com +84 902 881 833
World SteelBuilding trust, Assuring success

Ingegneria della protezione antincendio · articolo 2 di 10

How does intumescent paint work?

From a thin film to an insulating char: the chemistry and physics of intumescent coatings in a fire, and why expansion and performance are specific to each product.

Team tecnico World Steel · Aggiornato il 2026-10-16 · Lettura: 2 min

Intumescent coating expanding into char (illustration)

Three ingredients working together

A typical intumescent formulation contains an acid source (often a phosphate), a carbon source (a polyol) and a blowing agent (for example a melamine compound), held in a binder that softens when heated.

  1. The binder softens and the acid source decomposes.
  2. The acid reacts with the carbon source to form a carbon-rich char.
  3. The blowing agent releases gases that foam the softened mass.
  4. The result is a thick, porous char with low thermal conductivity.

The degree of expansion, the char strength and the insulation are specific to each product and are only known from its fire tests.

What the char does

The char is an insulating blanket between the fire and the steel. Heat still passes through, but much more slowly, so the steel temperature rises gradually. The coating is designed so that the steel stays below its critical temperature for the rated time.

Cellulosic and hydrocarbon fires

Building fires follow the standard (cellulosic) fire curve – ISO 834, ASTM E119, AS 1530.4. Hydrocarbon pool fires heat up much faster and hotter (UL 1709, EN 1363-2), and jet fires add erosion. Thin-film building intumescents are not designed for these conditions – epoxy systems tested for hydrocarbon and jet fires are.

What decides performance

  • Dry film thickness – more coating, more char.
  • Section factor – how fast the member heats up.
  • Critical steel temperature – the target the steel must stay below.
  • Section shape – open sections and hollow sections are tested separately.

FAQ

At what temperature does intumescent coating start to expand?

Typically from around 200–250 °C, but the exact activation temperature depends on the product.

Does the char fall off?

A correctly applied and certified system keeps a stable char for the tested duration; char stickability is part of the fire test.

Vi servono spessori e costi per il vostro progetto?Inviate l'elenco elementi e le classi di resistenza al fuoco – i nostri ingegneri preparano un'offerta di protezione antincendio.
Richiedi un'offerta

Preliminary calculations are provided for estimation purposes only. Final coating thickness and fire protection system selection must be verified against the approved product documentation, applicable project requirements and relevant engineering assessments.

Prossimo progetto

Progettate una struttura in acciaio all'estero?

Inviateci i vostri disegni o il modello IFC – il nostro ufficio preventivi risponde con ambito di fabbricazione, tempistiche e prezzo reso a destino.