신뢰 구축, 성공 보장 고객 포털 dang.victor@worldsteelgroup.com +84 902 881 833
World SteelBuilding trust, Assuring success

내화 엔지니어링 · 10편 중 10번째 기사

International fire protection standards for structural steel

EN 13381-8, EN 13501-2, BS 476, ASTM E119, UL 263, UL 1709 and AS 1530.4 – what each standard does, and the difference between fire tests, classification, structural design and product approval.

World Steel 엔지니어링팀 · 2026-10-16 업데이트 · 2분 분량

Fire curve (illustration)

Four kinds of documents

Standards by role
RoleExamples
Fire test methodISO 834, EN 1363, EN 13381-8 / -4, BS 476-20/21, ASTM E119, UL 263, UL 1709, AS 1530.4
ClassificationEN 13501-2 (R, E, I)
Structural fire designEN 1993-1-2, AS 4100 Section 12, AISC 360 Appendix 4
Product approvalETA / CE marking via EAD 350402, UL listed designs, national assessments

Europe and the UK

Intumescents are tested to EN 13381-8, which produces the assessed thickness data; results are classified under EN 13501-2, and products obtain a European Technical Assessment under EAD 350402 for CE marking. The UK still references BS 476 but widely accepts EN 13381-8 data.

United States

Fire resistance is tested to ASTM E119 / UL 263; UL listed designs give the thickness for a member type and W/D. Hydrocarbon exposure uses UL 1709.

Australia and New Zealand

AS 1530.4 is the fire test, expressed as FRL; AS 4100 Section 12 covers the fire design of steel, including the limiting temperature and the exposed surface area to mass ratio ksm.

What this means for a project

The authority having jurisdiction decides which approvals are accepted. Check early that the selected product has accepted data for every rating, section shape and size in the schedule.

FAQ

Is a product with BS 476 data accepted in Europe?

Generally EN 13381-8 / ETA data is required for CE marking; BS 476 data is a UK national route.

프로젝트의 두께와 비용이 필요하신가요?부재 일람표와 내화 등급을 보내주시면 엔지니어가 내화 제안서를 준비합니다.
제안 요청

Preliminary calculations are provided for estimation purposes only. Final coating thickness and fire protection system selection must be verified against the approved product documentation, applicable project requirements and relevant engineering assessments.

다음 프로젝트

해외 철골 구조물을 계획 중이십니까?

도면 또는 IFC 모델을 보내주십시오. 견적팀이 제작 범위, 일정 및 인도 가격을 회신해 드립니다.