International fire protection standards for structural steel

EN 13381-8, EN 13501-2, BS 476, ASTM E119, UL 263, UL 1709 and AS 1530.4 – what each standard does, and the difference between fire tests, classification, structural design and product approval.

Équipe d'ingénierie World Steel · Mis à jour le 2026-10-16 · 2 min de lecture

Fire curve (illustration)

Four kinds of documents

Standards by role
RoleExamples
Fire test methodISO 834, EN 1363, EN 13381-8 / -4, BS 476-20/21, ASTM E119, UL 263, UL 1709, AS 1530.4
ClassificationEN 13501-2 (R, E, I)
Structural fire designEN 1993-1-2, AS 4100 Section 12, AISC 360 Appendix 4
Product approvalETA / CE marking via EAD 350402, UL listed designs, national assessments

Europe and the UK

Intumescents are tested to EN 13381-8, which produces the assessed thickness data; results are classified under EN 13501-2, and products obtain a European Technical Assessment under EAD 350402 for CE marking. The UK still references BS 476 but widely accepts EN 13381-8 data.

United States

Fire resistance is tested to ASTM E119 / UL 263; UL listed designs give the thickness for a member type and W/D. Hydrocarbon exposure uses UL 1709.

Australia and New Zealand

AS 1530.4 is the fire test, expressed as FRL; AS 4100 Section 12 covers the fire design of steel, including the limiting temperature and the exposed surface area to mass ratio ksm.

What this means for a project

The authority having jurisdiction decides which approvals are accepted. Check early that the selected product has accepted data for every rating, section shape and size in the schedule.

FAQ

Is a product with BS 476 data accepted in Europe?

Generally EN 13381-8 / ETA data is required for CE marking; BS 476 data is a UK national route.

Besoin de l'épaisseur et du coût pour votre projet ?Envoyez la liste des éléments et les degrés de résistance au feu – nos ingénieurs préparent une proposition de protection incendie.
Demander une offre

Preliminary calculations are provided for estimation purposes only. Final coating thickness and fire protection system selection must be verified against the approved product documentation, applicable project requirements and relevant engineering assessments.

Prochain projet

Un projet de structure métallique à l'étranger ?

Envoyez-nous vos plans ou votre maquette IFC – notre équipe de chiffrage vous répond avec le périmètre de fabrication, le planning et le prix rendu chantier.