Four kinds of documents
| Role | Examples |
|---|---|
| Fire test method | ISO 834, EN 1363, EN 13381-8 / -4, BS 476-20/21, ASTM E119, UL 263, UL 1709, AS 1530.4 |
| Classification | EN 13501-2 (R, E, I) |
| Structural fire design | EN 1993-1-2, AS 4100 Section 12, AISC 360 Appendix 4 |
| Product approval | ETA / CE marking via EAD 350402, UL listed designs, national assessments |
Europe and the UK
Intumescents are tested to EN 13381-8, which produces the assessed thickness data; results are classified under EN 13501-2, and products obtain a European Technical Assessment under EAD 350402 for CE marking. The UK still references BS 476 but widely accepts EN 13381-8 data.
United States
Fire resistance is tested to ASTM E119 / UL 263; UL listed designs give the thickness for a member type and W/D. Hydrocarbon exposure uses UL 1709.
Australia and New Zealand
AS 1530.4 is the fire test, expressed as FRL; AS 4100 Section 12 covers the fire design of steel, including the limiting temperature and the exposed surface area to mass ratio ksm.
What this means for a project
The authority having jurisdiction decides which approvals are accepted. Check early that the selected product has accepted data for every rating, section shape and size in the schedule.
FAQ
Is a product with BS 476 data accepted in Europe?
Generally EN 13381-8 / ETA data is required for CE marking; BS 476 data is a UK national route.
Preliminary calculations are provided for estimation purposes only. Final coating thickness and fire protection system selection must be verified against the approved product documentation, applicable project requirements and relevant engineering assessments.