Fire stopping around pipes and cables in a wall (illustration)

Fire protection · Fire stopping

Fire stopping – sealing every opening in a fire-rated wall or floor

A fire-rated wall is only as good as its weakest opening. Pipes, cables, ducts and joints pass through compartment walls and floors; fire stopping seals those openings so fire and smoke cannot spread – with collars, wraps, sealants, compounds and slabs tested as complete systems.

Request a quotationXem danh mục sản phẩm

E · I
Integrity and insulation
what a fire stop must keep
Tested systems
Product + wall + service
must match the detail
F · T ratings
US listings
ASTM E814 / UL 1479
Conlit®
ROCKWOOL range
supplied by World Steel
Penetration seals (illustration)

Penetration seals and joint seals

Penetration seals close the gap around services passing through a wall or floor. Plastic pipes need intumescent collars or wraps that crush the softening pipe shut; metal pipes and cables need insulation and sealants that stop heat being conducted through. Linear joint seals close movement joints, the head of walls and the gap between floor slab and curtain wall.

Every fire stop is a tested system: the product, the wall or floor type, the service (material, diameter, insulation) and the installation detail must match the test evidence – EN 1366-3/-4 in Europe, ASTM E814 / UL 1479 in the USA, AS 4072.1 with AS 1530.4 in Australia.

Tiêu chuẩn & tuân thủ

Standards for fire stopping

Most often specified in our export markets.

Europe

  • EN 1366-3Fire resistance tests for service installations – penetration seals
  • EN 1366-4Linear joint seals
  • EAD 350454 · EN 13501-2Assessment of penetration seals; classification (E, EI)
Tất cả tiêu chuẩn Europe →

United States

  • ASTM E814 · UL 1479Through-penetration firestops (F, T, L ratings)
  • UL 2079 · ASTM E2307Joint systems; perimeter fire barriers (curtain wall)
Tất cả tiêu chuẩn United States →

Australia & New Zealand

  • AS 1530.4 · AS 4072.1Fire tests; service penetrations and control joints
  • NCC Spec. 13 / C3.15Protection of openings and penetrations
Tất cả tiêu chuẩn Australia & New Zealand →

Nội dung chỉ mang tính tham khảo – chỉ dẫn kỹ thuật của dự án, phiên bản quy chuẩn được áp dụng và cơ quan có thẩm quyền là căn cứ quyết định.

Choose the seal

Which product for which service?

Typical uses – always follow the manufacturer's tested system details.

Fire stopping selection
OpeningTypical solution
Plastic pipes (PVC, PP, PE)Intumescent pipe collar or wrap
Metal pipesStone wool pipe insulation + sealant or compound
Cables and cable traysCoated stone wool slab, ablative coating, putty or compound
Large mixed openingsFirestop compound or coated slab
Linear joints, head of wallIntumescent or silicone sealant over stone wool backing
Slab edge / curtain wallStone wool curtain wall fire stop + smoke seal
Electrical boxesIntumescent putty pads

FAQ

Câu hỏi thường gặp

What is the difference between fire stopping and fire protection?

Fire protection keeps structural members strong in a fire; fire stopping seals openings in fire-rated walls and floors so fire and smoke cannot pass through.

Can I use any fire-rated sealant on any penetration?

No. The rating applies only to the tested combination of product, wall or floor, service and detail – follow the manufacturer's system.