How AS/NZS 5131 tolerances work: essential versus functional Class 1 and 2, the Appendix F tables, measurement, nonconformance and fabricator control.

Essential tolerances protect design capacity and stabilityFunctional tolerances cover fit-up and appearance, in Class 1 or Class 2Class 1 applies by default; Class 2 should be considered for CC3 and CC4Mill, fabrication and erection tolerances must all be metAn essential exceedance is corrected or accepted only by recalculation

The vocabulary of tolerances

AS/NZS 5131 defines a tolerance as the band between the permitted upper and lower limits of a dimension (Clause 3.1.30), and Clause 3.2 then names five types. Getting these terms right avoids most disputes between fabricator, erector and certifier.

Tolerance types in Clause 3.2 (our summary)
TermWhat it controlsWhere the values are
Manufacturing tolerance (3.2.5)Size and shape of mill products as producedProduct standards, via Tables F1.1–F1.4
Fabrication tolerance (3.2.3)Any tolerance checked during fabricationTables F2.1–F2.10
Erection tolerance (3.2.1)Any tolerance checked during or after erectionTables F3.1–F3.7
Essential tolerance (3.2.2)Limits that keep the design assumptions for strength and stability valid"Essential" column of each Appendix F table
Functional tolerance (3.2.4)Limits for other functions such as fit-up and appearance"Class 1" and "Class 2" columns

Manufacturing, fabrication and erection describe when a tolerance is checked; essential and functional describe why it matters. A single criterion, such as column inclination, can carry both an essential and a functional value.

Essential versus functional, Class 1 versus Class 2

Clause 12.1 explains the two families. Essential tolerances relate to mechanical resistance and stability and are broadly consistent with the imperfections assumed in AS 4100, AS 5100.6, AS/NZS 4600, AS 2327 and NZS 3404. Functional tolerances serve fit-up and appearance and come in two classes: Class 2 is stricter than Class 1.

  • Both essential and functional tolerances must be met – the functional class is not optional.
  • The class may be set in the construction specification or an application standard; where nothing is specified, Class 1 applies.
  • A note to Clause 12.1 recommends that designers consider Class 2 for CC3 and CC4.
  • Permitted deviations exclude elastic deflection under self-weight, which is assessed separately.
  • Tolerances accumulate: fabricated pieces must meet fabrication tolerances on top of the mill tolerances of the product, and the erected frame must meet erection tolerances on top of fabrication tolerances.

The specification may tighten or add tolerances. If it does, Clause 12.1 requires it to state the amendment, the parameters and limits for any special tolerance, and whether it applies to all components or only nominated ones. Tight tolerances should be reserved for the interfaces that need them – see specification and documentation.

How Appendix F is organised

Appendix F is normative and contains 21 tables in three groups. Each table lists the criterion, how it is measured and the permitted deviation in essential, Class 1 and Class 2 columns.

Structure of Appendix F
GroupTablesCovers
ManufacturingF1.1–F1.4Rolled, welded and hollow sections (deferring to AS/NZS 3679.1, 3679.2 and 1163), welded profile flanges, decking, press-braked profiles
FabricationF2.1–F2.10Member camber, sweep, length and end squareness; fitments, stiffeners and holes; components; plate girder flanges and webs; three-plate and box sections; trusses; stiffened plating; bridge decks
ErectionF3.1–F3.7Foundations and anchor bolts; frame set-out; columns; beams; crane runway girders; bridges; bridge decks

Illustrative key values

The selected values below show how the system works. They are not a substitute for the tables – refer to the current edition of AS/NZS 5131 for the full requirements and measurement conventions.

Selected Appendix F values (essential / Class 1 / Class 2)
CriterionEssentialClass 1Class 2Source
Unintended sweep of a beam or column, length LL/1000, min 3 mmL/750, min 5 mmL/750, min 3 mmTable F2.1, item 3
Hole position within a bolt group2 mm2 mm1 mmTable F2.2, item 6
Gap at a full-contact bearing splice0.5 mm over at least two-thirds of the area, 1.0 mm max locally––Tables F2.1 and F3.3, item 6
Centre-to-centre of adjacent anchor bolt groups–6 mm6 mmTable F3.1, item 4
Column position at base6 mm10 mm5 mmTable F3.3, item 1
Inclination of a single-storey column, height hh/500h/300h/500Table F3.3, item 3
Level of a beam at its end connection10 mm10 mm5 mmTable F3.4, item 1

Two lessons follow. First, Class 2 often halves the Class 1 value, which affects jigs, drilling and survey methods. Second, some essential limits are tighter than Class 1 – column inclination is an example – so meeting Class 1 alone does not guarantee compliance. For AESS 2–4, straightness is halved again (Clause 10.4(g); see AESS).

Measurement

Clause 12.2 points to Clause 13.4 for fabricated components and Clause 13.11 for erected steel; Appendix F adds that measurement accuracy is assessed to the relevant part of ISO 17123. For erected steel, Clauses 13.11.4–13.11.7 require methods and instruments from ISO 7976-1 and -2, chosen so their accuracy is small relative to the tolerance; temperature correction to a 20°C reference; and allowance for tape sag and slope, instrument error and column shortening under load. Each measured value must be within its permitted deviation, and the algebraic sum must not exceed the limit for the whole structure; for large or unusual structures a statistical (SRSS) approach is allowed. Measurements are taken near site connection nodes under self-weight unless specified otherwise. See erection and site work.

When a tolerance is exceeded

Clauses 12.3 and 12.4 are strict. Any deviation beyond the permitted value must be corrected until it is back within the limit. For essential tolerances alone, there is one alternative: the deviation may be accepted if the designer explicitly includes it in a revised capacity calculation to the relevant design standard. A fabricator has no authority to accept an essential exceedance itself.

In practice this means a nonconformance report, the measured values, a proposed disposition and the designer's written acceptance or a correction procedure. Corrections by heat must respect the temperature limits of Clause 14.7, and every disposition belongs in the quality records.

How a fabricator controls tolerances

Tolerance compliance is built in, not inspected in. Typical controls at a CC3 fabricator include:

  • Detailing: a 3D model that sets out holes and connection positions from common datums, with allowances for weld shrinkage and specified camber;
  • Production: CNC cutting and drilling for hole groups, fixtures and jigs for repeat assemblies, and welding sequences that limit distortion;
  • Inspection: calibrated tapes, squares and levels, first-piece checks, and dimensional inspection reports for critical dimensions as nominated in the ITP;
  • Interfaces: trial assembly at the works where the specification requires it (Clause 11.5.10), and comparison with the as-built anchor bolt survey before shipment.

For steel shipped from overseas, a fit-up problem found on site is costly. The class, special tolerances and survey data for existing supports should be agreed during detailing, not after the steel arrives.

审核检查清单

针对 AS/NZS 5131 的这一部分,工程师、建造商或审核员在 CC3 加工厂应核查的内容 – 以及应索取的证据。

条款 · CC核查内容证据
12.1 CC1–CC4The functional tolerance class (Class 1 default, Class 2 considered for CC3/CC4) and any special tolerances are identified at contract review.Construction specification, contract review record
12.1 CC1–CC4Incoming sections are checked against their product standard manufacturing tolerances.Mill certificates, receiving inspection records
12.2, 13.4 CC2–CC4Critical fabricated dimensions are measured and recorded against Tables F2.1–F2.10.Dimensional inspection reports, ITP
12.2, Appendix F CC1–CC4Measuring instruments are calibrated and their accuracy suits the tolerance being checked.Calibration register and certificates
Table F2.2 CC1–CC4Hole positions, hole group spacing and twist are controlled to the specified class.CNC drilling programs, hole position checks
Table F2.1, item 5 and 6 CC2–CC4Full-contact bearing ends and splices meet the essential limits.End squareness and contact splice measurements
11.5.10 CC1–CC4 (where specified)Trial assembly at the works is carried out and recorded where the specification requires it.Trial assembly record and survey
12.3, 12.4 CC1–CC4Exceedances are corrected, or essential exceedances accepted only by the designer's revised calculation.NCR register, designer's dispositions
13.11.4–13.11.7 CC2–CC4The erected structure is surveyed against Tables F3.1–F3.7 with appropriate methods.As-built survey, temperature-corrected readings

在我们的工厂

World Steel 如何执行

01Tolerances set at detailingWorld Steel details members in Tekla with connection positions and holes taken from the 3D model, so hole groups and setting-out are consistent between shop and erection drawings.
02CNC hole and profile controlWorld Steel uses CNC cutting and drilling to place hole groups and profiles to the tolerance class specified for the project.
03Measured and recordedWorld Steel's project ITP nominates the dimensional checks, with hold and witness points open to the client's inspector, and the results go into the pre-shipment inspection and handover dossier.
04Nonconformance to the designerWhere a measured deviation exceeds Appendix F, World Steel's quality system raises a nonconformance and seeks correction or the designer's written disposition before shipment.

常见问题

Which tolerance class applies if the specification is silent?

Class 1. Clause 12.1 makes Class 1 the default functional class when nothing is specified, and recommends that Class 2 be considered for CC3 and CC4. Essential tolerances apply in every case.

Is Class 2 always tighter than the essential tolerance?

No. Essential and functional values serve different purposes, and in some rows the essential limit is tighter than Class 1 – single-storey column inclination is an example (Table F3.3). Both must be satisfied.

Can an essential tolerance exceedance be accepted?

Only if the designer includes the actual deviation in a revised design capacity calculation (Clause 12.3). Otherwise it must be corrected. Functional exceedances must be corrected (Clause 12.4).

Do the tolerances include deflection from self-weight?

No. Clause 12.1 and Appendix F state that permitted deviations exclude elastic deformation under self-weight, which must be assessed separately. Erected steel is normally measured under self-weight only.