Intumescent · exterior exposure
Exterior-grade intumescent systems
Steel outside the building envelope needs an intumescent system proven to keep its fire performance after weathering.
- Exterior / semi-exposed
- Exposure
- EAD 350402 type X or Y
- Durability
- Primer + intumescent + topcoat
- System
由 World Steel 随您的钢结构建筑一并供应或单独供应 – 一份订单、一次发运、一个合作伙伴。
概览
关于Exterior-grade intumescent systems
The European assessment document EAD 350402 classifies reactive coatings for durability: type X for all conditions including exterior, type Y for internal and semi-exposed, Z1 and Z2 for internal conditions; EN 16623 sets durability requirements as well.
Exterior systems are usually solvent-based or epoxy intumescents with a compatible sealer or topcoat; the whole system – primer, basecoat and topcoat – is what was tested.
Corrosion protection of the steel underneath follows ISO 12944 for the environment.
主要优势
- Proven fire performance after weathering
- Protects exposed steel and canopies
- Works with ISO 12944 corrosion systems
- Shop or site application
World Steel · 建筑围护材料中心
我们如何在钢结构建筑中使用Exterior-grade intumescent systems
World Steel specifies the full coating system from blast cleaning to topcoat and applies it in the shop where practical.
Product-specific test reports, classification reports and certificates are supplied for the product selected for each project – this page describes the product type, not a certified product.
- 01与结构一同选型 – 厚度、密度和饰面与屋面、墙面及防火设计相匹配。
- 02工程量取自与钢构件、檩条和围护板相同的 3D 模型。
- 03与钢结构包一同包装发运 – 一份到场交货计划。
应用
Exterior-grade intumescent systems的应用场合
- External steel frames and canopies
- Open car parks and walkways
- Semi-exposed industrial structures
技术数据
Exterior-grade intumescent systems – 技术性能
Typical properties and standards
| 性能 | 单位 | 数值 |
|---|---|---|
| Durability | — | EAD 350402 types X / Y / Z1 / Z2 · EN 16623 |
| Fire test | — | EN 13381-8 · UL 263 · BS 476-20/21 · AS 1530.4 |
| Corrosion | — | ISO 12944 primer and topcoat compatible with the intumescent |
数值为制造商针对该市场公布的数据。订货前请务必核对最新数据表及项目所需的认证。
FAQ
常见问题
Can an interior intumescent be used outside with a topcoat?
Only if that complete system has been tested for exterior durability – otherwise choose an exterior-qualified system.
Is this product certified?
Certification belongs to a specific manufacturer’s product or tested system. We supply the test report, classification or listing accepted in your market for the product selected – it is confirmed per project, never assumed.