Building components · Primary framing

Endwall framing

Endwall framing in PEB: post-and-beam vs rigid-frame (expandable) endwalls, endwall columns and rafters, sizes, bracing, design checks and installation.

更新于 4 分钟阅读 在 3D 模型中查看 →

Endwall columns and endwall rafter of a pre-engineered building highlighted in a 3D model
Endwall framing closes the gable ends and supports the endwall cladding.

What endwall framing is

The endwall is the gable end of a pre-engineered building. Its framing supports the endwall cladding, resists wind pressure on the end of the building and carries a half-bay of roof load. There are two basic types:

  • Post-and-beam (non-expandable) endwall: a series of endwall columns pinned at both ends supports an endwall rafter that is a simple beam spanning between columns. It is light and economical.
  • Rigid-frame (expandable) endwall: a full interior rigid frame is placed at the end, with non-load-bearing endwall posts (wind columns) in front of it. The building can later be extended by removing the cladding and posts. Where two building blocks meet, double frames at the joint line are described under expansion joints.

Endwall columns are usually spaced at 5–8 m, matching the girt span, and also frame door and window openings.

Endwall options and when to use them
OptionDescriptionBest suited to
Post-and-beam endwallPinned endwall posts supporting a light endwall rafter, X-bracing in the wall planeBuildings with no planned extension; lowest cost
Expandable post-and-beam endwallPost-and-beam endwall with posts, rafter and anchor bolts sized so a future interior frame can be addedPossible extension, but minimum present cost
Rigid frame endwallFull interior frame at the end with wind posts and girts outside itPlanned extension; large endwall openings; cranes running to the end
Endwall with gable overhangPurlins or rafter stubs cantilever beyond the endwallWeather protection and architectural effect; see roof extensions
Open endwallNo cladding; rigid frame or portal bracing for stabilitySheds, canopies, loading areas – design for internal pressure and wind under the roof
Masonry or precast endwallWall by others, tied to steel for lateral support or self-supportingFire walls and boundary walls; see masonry and precast interfaces

Endwall framing in the load path

Wind on the endwall acts on the cladding, then the girts, then the endwall columns. Each endwall column spans vertically from the slab to the roof and delivers its top reaction to the roof plane, where roof bracing carries it along the building to the braced bays and down to the foundations. The column base delivers the lower reaction directly to the slab or footing.

In a post-and-beam endwall, gravity load from the end half-bay of purlins goes to the endwall rafter and then directly down the endwall columns. In-plane forces on the endwall itself (wind on the side walls, seismic) are resisted by X-bracing or a diaphragm in the endwall plane.

Rod, cable and portal bracing types used in walls and roofs of a PEB
Endwalls are stabilised by bracing in their own plane.

Typical sections and sizes

Indicative endwall member types
MemberTypical sectionTypical size
Endwall column (light)Cold-formed C, single or back-to-back200–300 mm deep, 2.0–3.0 mm
Endwall column (tall or heavily loaded)Built-up or hot-rolled I-section250–600 mm deep
Endwall rafterCold-formed C or built-up I200–450 mm deep
Corner columnCold-formed C or built-up ISimilar to endwall column
Endwall bracingRod or cable X-bracing12–25 mm rods

Cold-formed sections use the same coil grades as purlins (for example ASTM A1011 / A653 Grade 50–55, AS 1397 G450, EN 10346 S350GD–S450GD); built-up members use 345–355 MPa plate.

Design considerations

  • Future expansion: if a building may be extended, specify an expandable rigid-frame endwall at the outset; converting a post-and-beam endwall later is expensive.
  • Wind columns: endwall columns in tall buildings are governed by deflection under wind; limits are often span/120 to span/240 depending on cladding type.
  • Top connection: endwall columns must transfer their wind reaction to the roof but should not pick up rafter deflection; slotted or flexible connections are used under expandable frames.
  • Large doors in endwalls interrupt columns and girts and need jamb and header framing designed for wind (see doors and framed openings); very wide openings may need a jack beam or header carrying the endwall rafter.
  • Endwall bracing may conflict with openings; portal bracing or a rigid endwall frame can be used instead.

Fabrication, coating and installation

World Steel roll-forms cold-formed endwall columns and rafters from galvanised coil and fabricates heavier endwall members on its built-up lines, with base, cap and clip plates welded and holes drilled from the 3D model. Galvanised cold-formed members need no further coating; built-up members follow the frame paint system.

On site, endwall columns are set on their anchor bolts, connected to the endwall rafter, plumbed and braced. Endwall girts are installed with the flanges oriented as shown on drawings, typically by-framed or flush with the column face. The endwall is checked for plumb before sheeting begins.

Common mistakes and quality checks

  • Expandable endwall not specified, leaving no way to extend without replacing framing.
  • Endwall column anchor bolts omitted from the foundation drawings – they are often smaller and overlooked.
  • Bracing removed to fit a door added late in design.
  • Endwall rafter not aligned with the roof plane, causing sheeting gaps at the gable trim.

Endwall wind loads are frequently the highest wall pressures on a building, especially near corners. Check the endwall zones in ASCE 7-22, NBC 2020, AS/NZS 1170.2 or EN 1991-1-4.

各地区标准

地区规范范围
United States AISI S100-16 / AISC 360-22Cold-formed and hot-rolled/built-up member design
Canada CSA S136-16 / CSA S16-19Cold-formed and structural steel design
Australia / NZ AS/NZS 4600:2018 / AS 4100:2020Cold-formed and structural steel design
Europe EN 1993-1-3 / EN 1993-1-1Cold-formed and general steel design

常见问题

What is an expandable endwall?

An expandable endwall uses a full rigid frame at the building end, so the endwall posts and cladding can be removed and new bays added later without rebuilding the frame.

Are endwall columns load-bearing?

In a post-and-beam endwall they carry roof gravity load and wind. In front of a rigid frame they act only as wind columns and should not pick up roof load.

How far apart are endwall columns?

Typically 5–8 m, set by the girt span and the positions of doors and windows.

What is an expandable post-and-beam endwall?

It is a post-and-beam endwall whose posts, rafter, connections and anchor bolts are sized so that a full interior frame can be added at the same line later. It costs a little more than a standard endwall but much less than a rigid frame endwall, and keeps the option of extending the building.