Boards · encasement systems
Steel encasement systems
Box encasement turns a steel member into a clean, square, fire-protected element – the details are as important as the board.
- Board + fixings + joints
- System
- Columns, beams, bracing
- Members
- Per tested system
- Rating
World Steel が鉄骨建築と一括で、または単体で供給 – 一つの注文、一つの出荷、一つのパートナー。
概要
Steel encasement systemsについて
A box encasement is built from fire boards fixed to noggins, steel angles or directly to each other around the section; the tested system defines board thickness, fixing spacing and joint treatment.
Boxed protection is sized using the boxed section factor (heated perimeter of the box) under EN 13381-4, BS 476-21 or ASTM E119 data.
Penetrations and connections to walls and slabs need tested details or firestop products.
主なメリット
- Clean, square architectural finish
- Dry, low-mess installation
- Long ratings achievable
- Inspectable thickness
World Steel · 外装材ハブ
鉄骨建築におけるSteel encasement systemsの活用
World Steel provides member schedules with boxed section factors and coordinates encasement details with the structure.
Product-specific test reports, classification reports and certificates are supplied for the product selected for each project – this page describes the product type, not a certified product.
- 01構造と一体で仕様決定 – 厚さ、密度、表面材を屋根・外壁・耐火設計に合わせます。
- 02数量は鉄骨、母屋、外装材と同じ 3D モデルから算出。
- 03鉄骨パッケージとともに梱包・出荷 – 現場への納入スケジュールは一つです。
用途
Steel encasement systemsの用途
- Columns in offices and public buildings
- Beams below fire-rated ceilings
- Steel in escape routes
技術データ
Steel encasement systems – 技術特性
Typical properties and standards
| 特性 | 単位 | 値 |
|---|---|---|
| Fire test | — | EN 13381-4 · BS 476-21 · UL 263 / ASTM E119 · AS 1530.4 |
| Design basis | — | Boxed section factor (Hp/A or W/D) |
| Components | — | Boards, noggins, angles, screws, staples, joint compound |
この市場向けにメーカーが公表している値です。ご注文前に必ず最新のデータシートと、プロジェクトに必要な認定をご確認ください。
FAQ
よくある質問
Why does the section factor change with boards?
Board encasement heats the steel through the box perimeter, so the boxed section factor is used – usually lower than the profile value, needing less protection.
Is this product certified?
Certification belongs to a specific manufacturer’s product or tested system. We supply the test report, classification or listing accepted in your market for the product selected – it is confirmed per project, never assumed.